General information |
Product type designation | SM AR02, AI RTD 2x16 bit |
CiR - Configuration in RUN |
Reparameterization possible in RUN | No |
Supply voltage |
Type of supply voltage | DC |
Rated value (DC) | 24 V; -15 / +20 % |
Input current |
Current consumption, typ. | 40 mA |
from backplane bus 5 V DC, typ. | 80 mA |
Power loss |
Power loss, typ. | 1.5 W |
Analog inputs |
Number of analog inputs | 2; Resistance thermometer |
permissible input voltage for voltage input (destruction limit), max. | 30 V |
Technical unit for temperature measurement adjustable | Yes; Degrees Celsius/degrees Fahrenheit |
Input ranges |
● Voltage | No |
● Current | No |
● Thermocouple | No |
● Resistance thermometer | Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Cu50, Cu100, LG-Ni1000 |
● Resistance | Yes; 48 Ω,150 Ω, 300 Ω, 600 Ω, 3 000 Ω, |
Input ranges (rated values), resistance thermometer |
● Cu 10 | Yes |
— Input resistance (Cu 10) | 10 Ω |
● Ni 100 | Yes |
— Input resistance (Ni 100) | 100 Ω |
● Ni 1000 | Yes |
— Input resistance (Ni 1000) | 1 000 Ω |
● LG-Ni 1000 | Yes |
— Input resistance (LG-Ni 1000) | 1 000 Ω |
● Ni 120 | Yes |
— Input resistance (Ni 120) | 120 Ω |
● Ni 200 | Yes |
— Input resistance (Ni 200) | 200 Ω |
● Ni 500 | Yes |
— Input resistance (Ni 500) | 500 Ω |
● Pt 100 | Yes |
— Input resistance (Pt 100) | 100 Ω |
● Pt 1000 | Yes |
— Input resistance (Pt 1000) | 1 000 Ω |
● Pt 200 | Yes |
— Input resistance (Pt 200) | 200 Ω |
● Pt 500 | Yes |
— Input resistance (Pt 500) | 500 Ω |
Input ranges (rated values), resistors |
● 0 to 48 ohms | Yes |
● 0 to 150 ohms | Yes |
● 0 to 300 ohms | Yes |
● 0 to 600 ohms | Yes |
● 0 to 3000 ohms | Yes |
Analog outputs |
Number of analog outputs | 0 |
Analog value generation for the inputs |
Measurement principle | Sigma Delta |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. | 15 bit; at 150, 300, 600 und 3 000 ohms; otherwise 15 bits + sign |
● Integration time, parameterizable | Yes; 10/ 16.67/ 20/ 100 ms |
● Interference voltage suppression for interference frequency f1 in Hz | 10 / 50 / 60 / 400 Hz |
Smoothing of measured values |
● parameterizable | Yes; In four stages by means of digital filtering |
● Step: None | Yes; 1x |
● Step: low | Yes; 4x |
● Step: Medium | Yes; 16x |
● Step: High | Yes; 32x |
Degree and class of protection |
IP degree of protection | IP20 |
Standards, approvals, certificates |
CE mark | Yes |
Dimensions |
Width | 45 mm |
Height | 100 mm |
Depth | 81 mm |
Weights |
Weight, approx. | 148.7 g |