$2219.69
$0.00
General information | ||
Product type designation | SB 1223, DI 2x5 V DC/DQ 2x5 V DC 200 kHz | |
Input current | ||
from backplane bus 5 V DC, typ. | 35 mA | |
Power loss | ||
Power loss, typ. | 0.5 W | |
Digital inputs | ||
Number of digital inputs | 2; Current-sourcing | |
● in groups of | 2 | |
Input voltage | ||
● Rated value (DC) | 5 V | |
● for signal "0" | (L+ minus 1.0 V DC) ... L+ | |
● for signal "1" | 0 V ... (L+ minus 2.0 V DC) | |
Input current | ||
● for signal "0", max. (permissible quiescent current) | 2.2 mA | |
● for signal "1", min. | 5.1 mA | |
● for signal "1", typ. | 15 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
— parameterizable | Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms | |
for interrupt inputs | ||
— parameterizable | Yes | |
for technological functions | ||
— parameterizable | Yes | |
Cable length | ||
● shielded, max. | 50 m; shielded, twisted pair | |
Digital outputs | ||
Number of digital outputs | 2; MOSFET, solid-state (current-sinking/current-sourcing) | |
● in groups of | 2 | |
Short-circuit protection | No | |
Switching capacity of the outputs | ||
● with resistive load, max. | 0.1 A | |
Load resistance range | ||
● upper limit | 7 Ω | |
Output voltage | ||
● Rated value (DC) | 5 V | |
● for signal "0", max. | 0.2 V | |
● for signal "1", min. | L+ minus 0.7 V DC | |
● for signal "1", max. | 6 V | |
Output current | ||
● for signal "1" rated value | 0.1 A | |
● for signal "1" permissible range, max. | 0.1 A | |
Cable length | ||
● shielded, max. | 50 m | |
Interrupts/diagnostics/status information | ||
Diagnostics indication LED | ||
● for status of the inputs | Yes | |
● for status of the outputs | Yes | |
Standards, approvals, certificates | ||
CE mark | Yes | |
CSA approval | Yes | |
UL approval | Yes | |
cULus | Yes | |
FM approval | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
Marine approval | Yes | |
Ambient conditions | ||
Free fall | ||
● Fall height, max. | 0.3 m; five times, in product package | |
Ambient temperature during operation | ||
● min. | -20 °C | |
● max. | 60 °C | |
● horizontal installation, min. | -20 °C | |
● horizontal installation, max. | 60 °C | |
● vertical installation, min. | -20 °C | |
● vertical installation, max. | 50 °C | |
Ambient temperature during storage/transportation | ||
● min. | -40 °C | |
● max. | 70 °C | |
Air pressure acc. to IEC 60068-2-13 | ||
● Storage/transport, min. | 660 hPa | |
● Storage/transport, max. | 1 080 hPa | |
Relative humidity | ||
● Operation at 25 ℃ without condensation, max. | 95 % | |
Mechanics/material | ||
Enclosure material (front) | ||
● Plastic | Yes | |
Dimensions | ||
Width | 38 mm | |
Height | 62 mm | |
Depth | 21 mm | |
Weights | ||
Weight, approx. | 35 g |