SIEMENS S7-300 SIMATIC S7 Safe analog input module Logical input SM 336 6ES7336-4GE00-0AB0

17 review

Product Code:

19145.58 0.00
SIMATIC S7, Analog input SM 336, 6 AI; 15 bit; fail-safe analog inputs for SIMATIC Safety, with HART support, up to Category 4 (EN 954-1)/ SIL3 (IEC61508)/PLE (ISO13849), 1x 20-pole
Quantity

Subtotal: $19145.58

Product details

Supply voltage
Rated value (DC)24 V
Reverse polarity protectionYes
Load voltage L+
● Rated value (DC)24 V
● Reverse polarity protectionYes
Input current
From power supply L+, typ.150 mA
from backplane bus 5 V DC, max.90 mA
Power loss
Power loss, typ.4.5 W
Analog inputs
Number of analog inputs6
permissible input current for current input (destruction limit), max.40 mA
Input ranges
● VoltageNo
● CurrentYes
● ThermocoupleNo
● Resistance thermometerNo
● ResistanceNo
Input ranges (rated values), currents
● 0 to 20 mAYes
— Input resistance (0 to 20 mA)150 Ω; typ. 150 ohms max. 175 ohms
● 4 mA to 20 mAYes
— Input resistance (4 mA to 20 mA)150 Ω; typ. 150 ohms max. 175 ohms
Cable length
● shielded, max.1 000 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max.16 bit; 15 bit + sign
● Integration time (ms)20 ms @ 50 Hz, 16.7 ms @ 60 Hz
● Interference voltage suppression for interference frequency f1 in Hzf=n x (f1 ±0.5 %)
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducerYes
● for current measurement as 4-wire transducerYes
Errors/accuracies
Operational error limit in overall temperature range
● Current, relative to input range, (+/-)0.2 %; 40 µA
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-)0.1 %
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
● Diagnostic alarmYes
Diagnoses
● Diagnostic information readableYes
Diagnostics indication LED
● Fail-safe operationYes
● Group error SF (red)Yes
● Encoder supply Vs (green)No
Potential separation
Potential separation analog inputs
● between the channelsYes
● between the channels and backplane busYes
● between the channels and the power supply of the electronicsYes
Isolation
Isolation tested with370V for 1 min
Standards, approvals, certificates
Highest safety class achievable in safety mode
● acc. to EN 9544
● Performance level according to ISO 13849-1e
● SIL acc. to IEC 61508SIL 3
connection method
required front connector20-pin
Dimensions
Width40 mm
Height125 mm
Depth120 mm
Weights
Weight, approx.350 g