Supply voltage |
Rated value (DC) | 24 V; 1L+ |
Reverse polarity protection | Yes |
Load voltage L+ |
● Rated value (DC) | 24 V; 2L+, 3L+ |
● Reverse polarity protection | No |
Input current |
from supply voltage 1L+, max. | 75 mA |
from load voltage 2L+ (without load), max. | 100 mA |
from load voltage 3L+ (without load), max. | 100 mA |
from backplane bus 5 V DC, max. | 100 mA |
Power loss |
Power loss, typ. | 12 W |
Digital outputs |
Number of digital outputs | 8 |
Short-circuit protection | Yes |
Limitation of inductive shutdown voltage to | L+ (-33 V) |
Switching capacity of the outputs |
● on lamp load, max. | 5 W |
Output voltage |
● for signal "1", min. | L+ (-1.0 V) |
Output current |
● for signal "1" rated value | 2 A |
● for signal "1" permissible range for 0 to 40 °C, min. | 7 mA |
● for signal "1" permissible range for 0 to 40 °C, max. | 2 A; 2 A for horizontal installation, 1 A for vertical installation |
● for signal "1" permissible range for 40 to 60 °C, min. | 7 mA |
● for signal "1" permissible range for 40 to 60 °C, max. | 1 A; for horizontal installation |
● for signal "0" residual current, max. | 0.5 mA |
Switching frequency |
● with resistive load, max. | 30 Hz |
● with inductive load, max. | 2 Hz |
● on lamp load, max. | 10 Hz |
Total current of the outputs (per group) |
horizontal installation |
— up to 40 °C, max. | 7.5 A |
— up to 60 °C, max. | 5 A |
vertical installation |
— up to 40 °C, max. | 5 A |
Cable length |
● shielded, max. | 200 m; 200 m for SIL 3, AK 6, Cat 4 |
● unshielded, max. | 200 m |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm | Yes; Parameterizable |
Diagnoses |
● Diagnostic information readable | Yes |
Diagnostics indication LED |
● Fail-safe operation | Yes |
● Group error SF (red) | Yes |
Potential separation |
Potential separation digital outputs |
● between the channels | Yes |
● between the channels, in groups of | 4 |
● between the channels and backplane bus | Yes |
● between the channels and the power supply of the electronics | Yes |
Isolation |
Isolation tested with | 500 V DC/350 V AC |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
● acc. to EN 954 | Cat. 4 |
● Performance level according to ISO 13849-1 | e |
● SIL acc. to IEC 61508 | SIL 3 |
connection method |
required front connector | 40-pin |
Dimensions |
Width | 80 mm |
Height | 125 mm |
Depth | 120 mm |
Weights |
Weight, approx. | 465 g |